tlUpsWatchdogSecsBeforeReboot OBJECT-TYPE
SYNTAX NonNegativeInteger
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum number of seconds that can expire between polls that
the engine makes to the UPS for data. If this time runs out, then
the UPS will cycle its outputs. Set this to zero to turns disable
this feature."
|
|