Description:
|
dcSystemTraps NOTIFICATION-GROUP
NOTIFICATIONS { alarmMajorHighBattVoltTrap,
alarmMinorHighBattVoltTrap,
alarmMajorLowBattVoltTrap,
alarmMinorLowBattVoltTrap,
alarmMajorBatteryHighTempTrap,
alarmMinorBatteryHighTempTrap,
alarmBatteryDisconnectOpenTrap,
alarmLVD1openTrap,
alarmLVD2openTrap,
alarmLVD3openTrap,
alarmACmainsTrap,
alarmBatteryBreakerOpenTrap,
alarmDistributionBreakerOpenTrap,
alarmMajorRectifierTrap,
alarmMinorRectifierTrap,
alarmMajorBatteryMidpointTrap,
alarmMinorBatteryMidpointTrap,
alarmBatteryLifeEndedTrap,
alarmBatteryTestmodeEnteredTrap,
alarmBatteryBoostmodeEnteredTrap,
alarmUserConfigurable1Trap,
alarmUserConfigurable2Trap,
alarmUserConfigurable3Trap,
alarmUserConfigurable4Trap,
alarmUserConfigurable5Trap,
alarmUserConfigurable6Trap,
alarmUserConfigurable7Trap,
alarmUserConfigurable8Trap,
alarmUserConfigurable9Trap,
alarmUserConfigurable10Trap,
alarmUserConfigurable11Trap,
alarmUserConfigurable12Trap,
alarmUserConfigurable13Trap,
alarmUserConfigurable14Trap }
STATUS current
DESCRIPTION
"This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs.
Each alarm condition is represented by a Alarm Condition Trap and an associated OFF
Trap, which is optionally transmitted according to the state of OID systemSendOffTrap"
|
|